As3000 Cable Selection ((top)) (2025-2026)

Before selecting a cable, you must calculate the ( Imaxcap I sub m a x end-sub

The circuit breaker or fuse must meet two conditions:

), which represents the highest current the circuit is likely to carry for a sustained period. as3000 cable selection

| Load (A) | Max C/B (A) | Minimum c.s.a. (mm²) | Voltage drop (mV/A/m) | |----------|-------------|----------------------|------------------------| | 10 | 10 | 1.0 | 44.0 | | 16 | 16 | 1.5 | 29.0 | | 20 | 20 | 2.5 | 18.0 | | 32 | 32 | 4.0 | 11.0 | | 40 | 40 | 6.0 | 7.3 | | 55 | 50 | 10.0 | 4.4 | | 70 | 63 | 16.0 | 2.8 |

| Requirement | Reference | Check | | :--- | :--- | :--- | | | AS3000 App B | Is the cable rated for the calculated load? | | 2. Derating | AS3008 | Have temperature and grouping been applied? | | 3. Voltage Drop | AS3000 2.6.2 | Is drop < 3% (Light) or < 5% (Power)? | | 4. Fault Loop | AS3000 2.6.3 | Is impedance low enough to trip the breaker? | | 5. Short Circuit | AS3000 2.5.2 | Will the cable survive a fault until the breaker trips? | | 6. Installation | AS3000 Sec 3 | Is the cable type suitable for the environment (e.g., UV exposure, water, mechanical damage)? | Before selecting a cable, you must calculate the

For most standard residential circuits, this is rarely the limiting factor, but it is mandatory for mains and sub-mains.

Note: Always verify with calculations.

$$I_z \ge I_n$$

The base ratings found in Step 1 assume "ideal" conditions. In reality, cables get hot, and heat cannot escape. You must apply derating factors found in and referenced in AS/NZS 3000 . Voltage Drop | AS3000 2

$$Z_s \le \fracU_0I_a$$