Short Ckt Current Calculation [2021]
The further away a fault is from the transformer or generator, the lower the current (because the wire itself adds impedance).
Choose a base apparent power ($MVA_{base}$) that is common throughout the system (commonly 10 MVA, 100 MVA, or 1 MVA).
$$I_{LL} = \frac{V_{LL}}{Z_{1} + Z_{2}}$$
“Exactly,” said Leo. “That breaker isn’t a protection device anymore. It’s a bomb. When that 72 kA fault occurs, the breaker will try to open, but the arc inside will be so violent it will vaporize the contacts, explode the casing, and turn the panel into a fireball. You won’t have a ‘short circuit.’ You’ll have a ‘long explosion.’” short ckt current calculation
To find the maximum fault current on the secondary side of a transformer, follow these steps:
Convert the ohmic value to per-unit using base impedance: $$Z_{pu} = \frac{Z_{ohms}}{Z_{base}}$$
This is the most straightforward approach, using Ohm's Law ( ). You calculate the total resistance ( ) and reactance ( The further away a fault is from the
): The sum of all resistances and reactances from the utility source down to the point of the fault. Transformer KVA and Impedance (
It ensures cables and motors don't catch fire before the protection kicks in. 4. Key Factors That Affect the Result
The maximum possible current (Peak) is: $$I_{peak} = I_{sym} \times K$$ “That breaker isn’t a protection device anymore
To calculate the fault current accurately, one must identify all contributing sources:
Larger transformers generally have lower impedance, leading to much higher potential fault currents.
Once the total per-unit impedance is found: $$I_{pu} = \frac{V_{pu}}{Z_{eq}}$$ (Note: $V_{pu}$ is typically assumed to be 1.0 p.u. for pre-fault voltage).